Specifications
A-6 TM-F1OP-C1XN-01
Additional Specifications
Input Conditions
Rise Time (No Load, Full Load):
a
a. Measured with stepped 0-10 V analog programming source and a resistive load.
6 V to 60 V models: 100 ms;
100 V to 600 V models: 170 ms
Fall Time (No Load):
a
6 V model: 1.5 s;
7.5 V to 60 V models: 3 s;
100 V to 600 V models: 4 s
Fall Time (Full Load):
a
6 V model: 10 ms;
7.5 V to 60 V models: 100 ms;
100 V to 600 V models: 170 ms
Voltage Mode Transient Response:
b
b. Time for the output voltage to recover within 0.5% of its rated value after a step change
in load current of 10% to 90% of rated output with an output setpoint between 50-100%
of rated value. Load slew rate <6 A/ms.
<3 ms
Time Delay from power on until
output stable
7 s maximum
Rated AC Input Voltage 100/120/200/220/230/240 Vac (nominal) ±10%
Maximum AC Input Power 2600 VA
Operational AC Input
Vo l t a g e
85-130 Vac or 190-264 Vac, 1φ;
6 V model: 95-130 Vac or 190-264 Vac, 1φ.
Auto range select function.
Maximum Input Current 20 A maximum at 120 Vac,
12 A maximum at 230 Vac.
Input Frequency Range 47-63 Hz
Power Factor 0.65 minimum at full load and 100 Vac input;
0.55 minimum at full load and 200 Vac input.