EasyManua.ls Logo

Ametek Sorensen XFR 1200 Watt Series - Electrical Specifications; Table A-1 Electrical Specifications for 6 V to 35 V Models

Ametek Sorensen XFR 1200 Watt Series
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Specifications
A-2 TM-F1OP-C1XN-01
Electrical Specifications
Table A-1
Electrical Specifications for 6 V to 35 V Models
Models 6-200 7.5-140 12-100 20-60 35-35
Output Ratings:
Output Voltage
a
Output Current
b
Output Power
0-6 V
0-200 A
c
1200 W
0-7.5 V
0-140 A
1050 W
0-12 V
0-100 A
1200 W
0-20 V
0-60 A
1200 W
0-35 V
0-35 A
1225 W
Line Regulation:
d
Voltage (0.01% of Vmax + 2 mV)
Current (0.01% of Imax + 2 mA)
2.6 mV
22 mA
2.75 mV
16 mA
3.2 mV
12 mA
4mV
8mA
5.5 mV
5.5 mA
Load Regulation:
e
Voltage (0.02% of Vmax + 5 mV)
Current (0.02% of Imax + 5 mA)
8.2 mV
45 mA
6.5 mV
33 mA
7.4 mV
25 mA
9mV
17 mA
12 mV
12 mV
Meter Accuracy:
Voltage (1% of Vmax + 1 count)
Current (1% of Imax + 1 count)
0.07 V
2.5 A
0.09 V
1.5 A
0.13 V
1.1 A
0.3 V
0.7 A
0.4 V
0.45 A
Output Noise (0-20 MHz):
Voltage (p-p) 75mV75mV75mV75mV120mV
Output Ripple (rms):
Voltage
Current
f
10 mV
750 mA
10 mV
500 mA
10 mV
500 mA
10 mV
500 mA
10 mV
300 mA
Drift (30 minutes):
g
Voltage (0.05% of Vmax)
Current (0.8% of Imax)
For Resistive Programming:
Voltage (0.6% of Vmax)
Current (0.6% of Imax)
3mV
2400 mA
36 mV
2400 mA
3.75 mV
1120 mA
45 mV
840 mA
6mV
800 mA
72 mV
600 mA
10 mV
480 mA
120 mV
360 mA
17.5 mV
280 mA
210 mV
210 mA
Drift (8 hours):
h
Voltage (0.05% of Vmax)
Current (0.05% of Imax)
For Resistive Programming:
Voltage (0.3% of Vmax)
Current (0.3% of Imax)
3mV
200 mA
18 mV
600 mA
3.75 mV
70 mA
22 mV
420 mA
6mV
50 mA
36 mV
300 mA
10 mV
30 mA
60 mV
180 mA
17.5 mV
17.5 mA
105 mV
105 mA
TM-F1OP-C1XN-01.book Page 2 Thursday, October 25, 2007 9:04 PM