Installation
2-14 TM-F1OP-C1XN-01
Load Wiring Length for Operation with Sense Lines
For applications using remote sensing, you must limit the voltage drop
across each load line. Figure 2-3 shows some allowable wire lengths for a
given load current and wire size. We recommend that you use the larger
load wiring to ensure a smaller voltage drop (1 V typical maximum),
although units will compensate for up to 5 V drop in each line. See also
“Local and Remote Sensing”.
.
Table 2-4
Current Carrying Capacity for Load Wiring
Wire Size
(AWG) Max. Current (A)
Wire Size
(AWG) Max. Current (A)
20 2.5 6 61
18 4 4 97
16 6 2 155
14 10 1 192
12 16 1/0 247
10 21 2/0 303
836
Figure 2-3
Maximum Load Wire Length for 1 V Line Drop
WIRE GAUGE (AWG)
16
14
12
10
8
6
4
2 1/0
1 2/0
WIRE LENGTH (FEET)
100
90
80
70
60
50
40
30
20
10
LOAD CURRENT (AMPS)
1
2
3
4
5
6
7
8
9
10
20
30
40
50
60
70
80
90
100
200
300
400
500
1000