EasyManua.ls Logo

Ametek Sorensen XFR 1200 Watt Series - Load Wiring Length for Operation with Sense Lines; Figure 2-3 Maximum Load Wire Length for 1 V Line Drop; Table 2-4 Current Carrying Capacity for Load Wiring

Ametek Sorensen XFR 1200 Watt Series
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation
2-14 TM-F1OP-C1XN-01
Load Wiring Length for Operation with Sense Lines
For applications using remote sensing, you must limit the voltage drop
across each load line. Figure 2-3 shows some allowable wire lengths for a
given load current and wire size. We recommend that you use the larger
load wiring to ensure a smaller voltage drop (1 V typical maximum),
although units will compensate for up to 5 V drop in each line. See also
“Local and Remote Sensing”.
.
Table 2-4
Current Carrying Capacity for Load Wiring
Wire Size
(AWG) Max. Current (A)
Wire Size
(AWG) Max. Current (A)
20 2.5 6 61
18 4 4 97
16 6 2 155
14 10 1 192
12 16 1/0 247
10 21 2/0 303
836
Figure 2-3
Maximum Load Wire Length for 1 V Line Drop
WIRE GAUGE (AWG)
16
14
12
10
8
6
4
2 1/0
1 2/0
WIRE LENGTH (FEET)
100
90
80
70
60
50
40
30
20
10
LOAD CURRENT (AMPS)
1
2
3
4
5
6
7
8
9
10
20
30
40
50
60
70
80
90
100
200
300
400
500
1000
TM-F1OP-C1XN-01.book Page 14 Thursday, October 25, 2007 9:04 PM

Table of Contents

Related product manuals