Octave Configuration Guide 18
Pulse Max Flow (per the set display units) – Limit the flow to a value that
ensures reliable pulse detection.
When the meter is connected to a 3/4
″ pipe and the units are cubic meters, the
recommended value is 8 m
3
/h. When the meter is connected to a 1″pipe and
the units are cubic meters, the recommended value is 12 m
3
/h.
Pulse 1
Mode – Set the pulse’s accumulated volume output mode:
• “Disable” – output is disabled
• “Net” – pulse output is a measure of forward volume minus reverse
volume
• “Forward” – pulse output is a measure of forward volume
• “Reverse” – pulse output is a measure of reverse volume
• “Forward & Reverse” – pulse output includes a measure of both
forward volume and reverse flow for control devices that support
input of two pulse data streams through a single input channel
Resolution (unit) - Set the pulse resolution, i.e. the volume per one pulse, for
the selected measurement unit:
• 0.001
• 0.01
• 0.1
• 1
• 10
• 100
• 1000
• 10000
NOTE: The available resolution values are influenced by the value set for the
Pulse Max Flow parameter.