Signal DIN 2 M0120 = CLOSE
Signal DIN 3 M0119 = OPEN
Information
The logic for the digital inputs may be inverted. Depending on the parameter setting
(e.g. Coding DIN 7 M0393), the input is either High active or Low active. Default
setting is High active.
Example of digital output configuration
Required user level: Specialist (4)
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Master actuator (MA)
Only the outputs used for control of the slave actuator are listed, the outputs to the
DCS are preset as standard (e.g.End position CLOSED, End position OPEN, Selector
sw. REMOTE, Failure (Cfg))
Use output DOUT 8 for signal LPV SA-CLOSE,
Use output DOUT 9 for signal LPV SA-OPEN,
Use output DOUT 10 for signal LPV Sync Out,
Setting values:
Signal DOUT 8 M0398 = LPV run CLOSE (SA)
Signal DOUT 9 M0399 = LPV run OPEN (SA)
Signal DOUT 10 M0400 = LPV Sync Out
Slave actuator (SA)
Use output DOUT 1 for signal System ok,
Use output DOUT 2 for signal End position CLOSED,
Use output DOUT 3 for signal LPV Sync Out,
Use output DOUT 4 for signal Selector sw. REMOTE,
Setting values:
Signal DOUT 1 M0109 = System ok
Signal DOUT 2 M0115 = End position CLOSED
Signal DOUT 3 M0114 = LPV Sync Out
Signal DOUT 4 M0113 = Selector sw. REMOTE
Information
The logic for the digital outputs may be inverted. Depending on the parameter setting
(e.g. Coding DOUT 1M0102), the input is either High active or Low active. Default
setting is High active.
8.12.1. LPV function: activate
Required user level: Specialist (4) or higher.
Device configuration M0053
Application functions M0178
Activation M0212
LPV function M1087
Default value: Function not active
Setting values:
Function not active
Function deactivated.
Function active
Function activated.
8.12.2. LPV actuator type: configure
Required user level: Specialist (4) or higher.
When using the LPV function, it must be defined for each actuator controls whether
it controls the master or the slave actuator.
70
Actuator controls
Application functions AC 01.2/ACExC 01.2 Profinet