Customer settings M0041
Lift Plug Valve M1089
Sel. master/slave act. M1090
Default value: MA master actu./rotat.
Setting values:
MA master actu./rotat.
Actuator controls/actuator act as master actuator is in charge of the rotation of the
closing element.
SA slave act./stroke
Actuator controls/actuator act as slave actuator is in charge of the stroke of the
closing element.
8.12.3. Delay time of LPV master actuator: configure
Configure delay time for operation in direction OPEN
A delay time for operation in direction OPEN can be defined in end position CLOSED
of the master actuator. When reaching end position OPEN of the slave actuator, the
procedure for opening valve will be delayed by this time.The master actuator will
then run in direction OPEN.
Required user level: Specialist (4) or higher.
Customer settings M0041
Lift Plug Valve M1089
Delay MA direct.OPEN M1091
Default value: 02:00.0
Setting ranges: 00:00.0 ... 15:00.0 min:s (minutes:seconds)
Configure delay time for operation in direction CLOSE
A delay time for operation in direction CLOSE can be defined in end position OPEN
of the master actuator. When reaching end position OPEN of the slave actuator, the
procedure for closing valve will be delayed by this time.The master actuator will then
run in direction CLOSE.
Required user level: Specialist (4) or higher.
Customer settings M0041
Lift Plug Valve M1089
Delay MA direct.CLOSE M1092
Default value: 00:00.0
Setting ranges: 00:00.0 15:00.0 min:s (minutes:seconds)
8.12.4. Delay time of LPV slave actuator: configure
A delay time for operation in direction CLOSE of the slave actuator can be defined
in end positions OPEN and CLOSED of the master actuator. When reaching end
positions OPEN or CLOSED of the master actuator, the procedure for valve opening
or closing will be delayed by this time.The slave actuator will then run in direction
CLOSE.
Required user level: Specialist (4) or higher.
Customer settings M0041
Lift Plug Valve M1089
Delay SA direct.CLOSE M1093
Default value: 00:00,0
Setting ranges: 00:00.0 ... 15:00.0 min:s (minutes:seconds)
8.13. Automatic deblocking
Requirements
This function requires one of the following equipments within the actuator:
Electronic control unit
71
Actuator controls
AC 01.2/ACExC 01.2 Profinet Application functions

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUMA AC 01.2 and is the answer not in the manual?

AUMA AC 01.2 Specifications

General IconGeneral
BrandAUMA
ModelAC 01.2
CategoryControl Unit
LanguageEnglish

Related product manuals