Default value: 0.0 °
Setting range: 0.0° ... 360.0° (degree)
9.3.8. Torque switching: by-pass
If an EMERGENCY operation is initiated, the torque switches can be by-passed
during this operation.
Required access level: Specialist (4) or higher.
Customer settings M0041
EMCY behaviour M0198
By-pass torque M0199
Default value: Off
Setting values:
Off
No by-pass of the torque switching.
On
The signals of the torque switching in the actuator are by-passed.
9.3.9. Motor protection: by-pass
If an EMERGENCY operation is initiated, the motor protection can be by-passed
during this operation.
Required user level: Specialist (4) or higher.
Customer settings M0041
EMCY behaviour M0198
Thermal by-pass M0200
Default value: Off
Setting values:
Off
No by-pass of motor protection.
On
The signals of the thermoswitches or the PTC thermistors of the motor winding are
by-passed.
Information
It is not possible to by-pass the motor protection for actuators with explosion protec-
tion.
9.3.10. Stepping mode: by-pass
If an EMERGENCY operation is initiated, stepping mode can be by-passed during
this operation.
Required user level: Specialist (4) or higher.
Customer settings M0041
EMCY behaviour M0198
By-pass timer M0201
Default value: Off
Setting values:
Off
No by-pass of stepping mode.
On
Stepping mode is by-passed.
9.3.11. Operation profile: by-pass
If an EMERGENCY operation is initiated, the pre-set operation profile (operation
behaviour) can be by-passed.
Required user level: Specialist (4) or higher.
Customer settings M0041
EMCY behaviour M0198
By-pass operat.profile M0596
81
Actuator controls
AC 01.2/ACExC 01.2 Profinet Failure functions