9.5.1. Priority REMOTE: activate
Required user level: Specialist (4) or higher.
Device configuration M0053
Application functions M0178
Activation M0212
Priority REMOTE M0770
Default value: Function not active
Setting values:
Function not active
<Priority REMOTE> function is deactivated.
Function active
<Priority REMOTE> function is activated.
9.5.2. Priority REMOTE behaviour
This function determines which selector switch function (LOCAL, OFF) requires an
additional enable signal.
Required user level: Specialist (4) or higher.
Customer settings M0041
Local controls M0075
Priority REMOTE M0773
Default value: Sel. sw. Local
Setting values:
Sel. sw. Local
Priority of control from REMOTE is only effective in operation mode LOCAL (selector
switch is in position Local control). If no enable signal is present, operation via push
buttons on the local controls is disabled and the actuator can be controlled from
REMOTE.The actuator controls indicates the symbol in the status line of the
display (menu S0001).
Sel. sw. Local + Off
Priority of control from REMOTE is effective in operation modes LOCAL and OFF
(selector switch positions Local control and 0). If no enable signal is present,
operation via push buttons on the local controls is disabled and the actuator can be
controlled from REMOTE.The actuator controls indicates the symbol in the status
line of the display (menu S0001).
9.5.3. Fieldbus auto enable
Properties
Generating an enable signal for the <Priority REMOTE> function in case of fieldbus
communication failure
Condition
<Priority REMOTE> function.
Customer settings M0041
Local controls M0075
Fieldbus auto enable M0774
Default value: On
Setting values:
Off
<Fieldbus auto enable> function is deactivated. In case of bus failure, NO enable
signal is generated via fieldbus (command Fieldb. enable LOCAL = 0). <Priority
REMOTE> function is active and operation vial local controls disabled.
On
In case of bus failure, the actuator controls generate the enable signal themselves
to be able to operate the actuator locally.
9.6. Interlock (enabling operation commands)
Characteristics
An operation command will only be executed if an additional enable signal for
the operation command is present.
85
Actuator controls
AC 01.2/ACExC 01.2 Profinet Failure functions

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUMA AC 01.2 and is the answer not in the manual?

AUMA AC 01.2 Specifications

General IconGeneral
BrandAUMA
ModelAC 01.2
CategoryControl Unit
LanguageEnglish

Related product manuals