Default value: Off
Setting values:
Off
No by-pass of operation profile.
On
The operation profile is by-passed.
9.3.12. Interlock: by-pass
If the Interlock function is activated, you may by-pass this function during
EMERGENCY operation to prevent that an enable command must be issued to
perform EMERGENCY operation.
Required user level: Specialist (4) or higher.
Customer settings M0041
EMCY behaviour M0198
By-pass Interlock M0668
Default value: Off
Setting values:
Off
By-pass mode is deactivated. Interlock function is even active during EMERGENCY
operation.
On
By-pass mode is activated. Interlock function is deactivated during EMERGENCY
operation.
9.3.13. Local stop: by-pass
If activated, you may by-pass Local Stop function during an EMERGENCY operation
to prevent interruption of EMERGENCY operation by pressing the push button STOP.
Required user level: Specialist (4) or higher.
Customer settings M0041
EMCY behaviour M0198
By-pass Local STOP M0682
Default value: Off
Setting values:
Off
By-pass mode is deactivated. Local Stop function is even active during EMERGENCY
operation.
On
By-pass mode is activated. Local Stop function is deactivated during EMERGENCY
operation.
9.3.14. Delay time for EMERGENCY operation
An EMERGENCY operation is only performed once the delay time has expired.
Consequently, a short-term signal failure will not have an impact on the process and
will not immediately initiate an EMERGENCY operation.
Required user level: AUMA (6) or higher.
Customer settings M0041
EMCY behaviour M0198
Delay time M0804
Default value: 00:01.00 min : s
Setting range: 00:00.0 ... 30:00.0 min : s
9.4. Enable local controls
Application
Protection against unauthorised operation via local controls
Protection against unauthorised parameter setting via local controls
Properties
The selector switch functions LOCAL and/or OFF may be enabled or disabled.