Electrical data
Instruction handbook b maXX 5000
Document No.: 5.09021.16 Baumüller Nürnberg GmbH
68
of 328
3.4
m Single axis unit safety
BM532
6 BM5326-A BM5327 BM5327-A
Input rated power
1)
6.7 kW 11.2 kW
Input rated current (I
eff
)
1)
10.5 A 17.5 A
DC link voltage (U
DC
)
1)
60 V - 760 V
DC link capacitance (internal) 165 µF 330 µF
DC link discharge time
(internal DC link capacitance)
300 s
Output voltage
(U
AC
)
1) 3)
0 - 500 V
Output frequency at 4 kHz
4)
0 - 450 Hz
Output rated current
(I
AC
RMS)
1) 2) 5)11)
at 4 kHz
4)
12 A 20 A
Output rated current (I
AC
RMS)
1) 2) 5)11)
at 8 kHz
4)
8.4 A 14 A
Output rated current (I
AC
RMS)
1) 2) 5)11)
at 16 kHz
4)
4.8 A 8 A
Output peak current
(I
AC
RMS)
1) 5) 6)11)
at 4 kHz
4)
24 A 40 A
Output peak current
(I
AC
RMS)
1) 5) 6)11)
at 8 kHz
4)
16.8 A 28 A
Output peak current
(I
AC
RMS)
1) 5) 6)11)
at 16 kHz
4)
9.6 A 16 A
Short-time operation KB 200 %
Max. length of time peak current
6) 10)
Refer to
ZLoa
d cycle according EN61800-6as from page 75
Power loss with regard to power supply Max. 105 W Max. 155 W
Power loss with regard to
control voltage supply
(air-cooled)
7)
Max. 39 W Max. 41 W
Power loss with regard to
control voltage supply
(cold plate cooling)
7)
Max.
37 W
- Max.
37 W
-
Current of the integrated brake control
(option)
8)
Max. 4.0 A
Cooling air requirement power heat sink 10 m
3
/h - 20 m
3
/h -
Cooling air velocity power heat sink > 5 m/s > 5 m/s
Cooling air requirement internal space of device 10 m
3
/h - 10 m
3
/h -
Footnotes refer to Zpage 73.

Table of Contents

Related product manuals