Design and Operation
Instruction handbook b maXX 5000
Document No.: 5.09021.16
89
of 328
4
ZFuses– as from page 261
n Devices are suit
able for use on a circuit capable of delivering not more than
50000 rms symmetrical amperes, 480 Volt maximum, when protected by J Class
fuses rated
n BM5031/B
M5032:
branch circuit protection fuse rating: 600 V / max. 60 A
n BM5043/B
M5044/BM5174
branch circuit protection fuse rating: 600 V / max. 150 A
n Fuses mu
st be installed on the line side of the mains rectifier (BM50XX,
BM51XX)
n Integral so
lid state short circuit protection does not provide branch circuit
protection. Branch circuit protection must be provided in accordance with the
Manufacturer Instructions, National Electrical Code and any additional local
codes.
ZElectrical data BM50X
X; BM51XX– as from page 58
n Mains rect
ifiers BM50XX, BM51XX are not provided with DC link preventing over-
loading. Total capacity of all axis units BM53XX connected to the mains recti-
fier shall not exceed the rectifiers rating.
ZMo
unting of the DC link bar– as from page 116 and ZDC link bar– on page 287
n Proper installa
tion of the DC link bar, refer to ZMounting of the DC link bar– as from
page 116 and prop
er DC link bar refer to ZDC link bar– on page 287.