14 ATICS-2-ISO_D00046_04_M_XXEN / 03.2021
System description
3.2 Functional safety
Functional safety according to IEC 61508 guarantees safety from risks due to malfunction when used
properly. The ATICS® is suitable for use in safety-related systems according to SIL2. SIL stands for "Safety
Integrity Level".
3.2.1 Product life-cycle management
Safety must be guaranteed over the entire life cycle, from the time it is designed, developed, manufac-
tured, commissioned, maintained to the time it is taken out of service. Responsibility during the life cy-
cle:
For detailed information refer to:
• Chapter „Commissioning, settings and testing“ on p. 45.
• chapter „Periodic verification and service“ on p. 89.
3.3 Application examples
3.3.1 Application example operating theatre
• ATICS-2-63A-ISO: Changeover be-
tween the preferred and redun-
dant line while monitoring the
medical IT system with transform-
er load and temperature monitor-
ing
• IR426-D47: Monitoring of the op-
erating theatre light IT system
(optional)
• MK2430/MK800/TM800/CP9xx:
Alarm at at least two points with
independent power supplies for
functional safety
Production Commissioning RecyclingDecommissioningMaintenance
Bender plant operator Bender
U
1
U
2
U
3
I
3
I
L
R
ISO
T
ATiCS-2-63A-ISO
ϑ
2 2
BSV
BMS
MK
IR426-D47
TM800
supply line
supply line
Nurse desk