70 ATICS-2-ISO_D00046_04_M_XXEN / 03.2021
Menu mode: Operation and setting
Selecting a line:
1. Use the "
" arrow button to go to the line setting. Press the " " button.
2. Use the arrow buttons to select one line (voltage 1, 2) or both lines (voltage 1…2). Press the "
" button to confirm your selection.
Setting voltage for one line: Setting voltage for both lines:
Adjusting the settings:
Menu Description
Exit Exit settings menu "Voltage"; go up one menu level
1. Undervolt. Undervoltage; setting range: 160…207 V (278 V…360 V)*
2. Overvolt. Overvoltage; setting range: 240…275 V (417 V…478 V)*
3. t(on) Response delay**:
Setting range: 50 ms…100 s
Resolution of settings: 50 ms / 100 ms / 1 s / 5 s / 10 s
4. t(off) Delay on release**:
Setting range: 200 ms…100 s
Resolution of settings: 50 ms / 100 ms / 1 s / 5 s / 10 s
5. Hysteresis Setting range: 2…10 %
Resolution of setting: 1 %
* Values for ATICS…400 versions
** Observe also the time diagrams
7.3.4.3 Settings menu 3: Current
In this menu, you can adjust settings for current monitoring (short-circuit detection) downstream of the
transfer switching and monitoring device (TN system). The current is detected via a measuring current
transformer (T3 in the connection example P. 33).
Voltage: 1 . . 2
Exit
1. Undervolt.: 184V
2. Overvoltage: 250V
Voltage: 2
Exit
1. Undervolt.: 184V
2. Overvoltage. 250V