60 ATICS-2-ISO_D00046_04_M_XXEN / 03.2021
Operation
Menu Description
Exit Exit "Changeover" reset menu; go up one menu level
1. Changeover: xxx Number of changeovers performed
2. Alarm: 8000 Alarm value for maximum number of changeovers performed*
Delete Increase alarm value by 500 changeovers
4. Operat. time: xxh Operating hours counter (h=hours, d=days, mo=months)
5. Alarm: 120mo Alarm value for maximum number of operating hours (prewarning after 108
months)*
Delete The limit value for the permissible number of operating hours is increased by 13
months.
The value is automatically increased by 13 months if the alarm has already been
cleared once before and a successful test of the changeover process is carried out.
7: Changeover I>: 0 Number of changeovers performed which were carried out with overcurrent of
short-circuit current
(see chapter „Menu 2: Changeover“ on p. 64)
8. Alarm: 1 Alarm value for maximum permitted number of changeovers performed which
were carried out with overcurrent or short-circuit current*
Delete Increase alarm value for changeover in case of overcurrent or short-circuit current
by 1 changeover
* for functional safety according to IEC 61508-2:2010
Delete Set new alarm value. Clear alarm.
Cancel Return to reset menu
6.2.4.4 Reset menu 4: Service alarm
• Resetting the service prewarning suppresses the service prewarning until the next service ap-
pointment.
• Resetting the service alarm sets the date for the next service appointment to "current date +
service interval".
Delete
Cancel
Delete