EasyManua.ls Logo

Bender ATICS-2-63A-ISO - Reset Menu 2: Switchbacklock; Reset Menu 3: Changeover

Bender ATICS-2-63A-ISO
104 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ATICS-2-ISO_D00046_04_M_XXEN / 03.2021 59
ATICS-2-63A-ISO
6.2.4.2 Reset menu 2: SwitchBackLock
Delete Disable the switch-back lock of the changeover function. The progress of the test is shown on
the display. The device switches back to the redundant line.
Cancel Return to reset menu
i
There are different possibilities to disable the switch-back lock via gateway (COM4xx, CP700 etc.):
• Via menu: Select "RESET > Switch-back lock". Requirement: Parameter setting must be possible
(menu "Settings > Interface > Settings > On").
• Via Modbus control commands: Using the command "Changeover to line 1 or line 2".
Testing must be enabled (menu "Settings > Interface > Test > On").
6.2.4.3 Reset menu 3: Changeover
I
Caution! With increasing service life, the probability of component failure increases for every
technical product.
For operation according to IEC 61508-2, additional limit values are monitored (number of switching
cycles, operating time, number of switching cycles in the event of a short circuit). If the set limit va-
lues are exceeded, the device displays a prewarning or an alarm.
The alarm can be "deleted" by increasing the limit values.
To ensure continued operation in accordance with the IEC 61508-2 standard, the device must be re-
placed.
i
Regardless of the IEC 61508-2 standard, the safe function of the device is of course still guaranteed
due to the cyclical self-monitoring functions.
Operation in accordance with DIN VDE 0100-710, DIN VDE 0100-718 or IEC 60364-7-710 is still possi-
ble if the prescribed measures are implemented (see chapter „Periodic verification and service“ on p.
89).
Delete
Cancel
Delete

Table of Contents