EasyManua.ls Logo

Bender ATICS-2-63A-ISO - Menu 1: Alarm;meas.values

Bender ATICS-2-63A-ISO
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ATICS-2-ISO_D00046_04_M_XXEN / 03.2021 63
ATICS-2-63A-ISO
7.3 Function of the main menu
Menu item Function Page
Exit Exit menu mode
1. Alarm/meas.values Display saved status messages, alarm messages and measured values
P. 63
2. Changeover Display information on the changeover function (number, test)
P. 64
3. History/Loggers Display history memory, data logger, configuration logger, test logger and
service logger
P. 65
4. Settings Various settings for this device
P. 66
5. Control Run TEST and RESET of this device
P. 80
6. Dig. input Display voltage level of the digital input
P. 81
7. Info Display information on device type and firmware versions
P. 81
7.3.1 Menu 1: Alarm/meas.values
Display current status messages, alarm messages and measured values. The device shows the alarm
status for each menu item:
= no alarm, = alarm.
Menu Description
Exit Exit "Alarm/meas. values" menu; go up one menu level
1.
Line 1: 228V
Line 1: Measured value mains voltage
2.
Line 2: 183V
Line 2: Measured value mains voltage
3.
Position: 1
Switch position of the automatic transfer switching device
4.
t(2->1):--
or
4.
Switch-back lock
Return transfer delay time is enabled, seconds counting backwards
or
Switch-back lock enabled
5.
Automatic mode
Automatic mode or manual mode
6.
Status
Device error (e.g.: no BMS bus master present)
7.
I(3):35A
Load current downstream of the transfer switching and monitoring device I(3) or
"CT connection" fault
8.
Dig. input:--
Alarm digital input 1
(see chapter „Settings menu 6: Dig. input“ on p. 74)
9.
Insulation:-
155kOhm
Measured value of insulation resistance
10.
Load: 55%
Display of the load in the IT system in %. The maximum load current is adjustable.
If a "CT connection" or "CT short-circuit" fault occurs, it will be displayed here.
11.
Temperature
Overtemperature of the IT system transformer
12.
Faultlocat.:---
EDS, Start

Table of Contents