EasyManua.ls Logo

Bender ATICS-2-63A-ISO - Messages with Error Code or Service Code

Bender ATICS-2-63A-ISO
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ATICS-2-ISO_D00046_04_M_XXEN / 03.2021 85
ATICS-2-63A-ISO
8.1.2 Messages with error code or service code
Error code/service
code
Description Action
1.xx, 4.xx, 9.xx Fault message from the internal memory
monitoring.
Contact the Bender service.
3.10 Prewarning
The max. number of operating hours will be
reached in one year
For functional safety SIL 2 require-
ments according to IEC 61508-2,
the replacement must be planned.
Alarm can be acknowledged (see
chapter „Reset menu 3: Changeo-
ver“ on p. 59)
3.11 Maximum number of operating hours
exceeded for functional safety according to
IEC 61508-2:2010.
For functional safety SIL 2 require-
ments according to IEC 61508-2, the
replacement must be carried out.
Alarm can be acknowledged
(see chapter „Reset menu 3: Change-
over“ on p. 59)
3.12 Maximum number of changeovers
exceeded.
Plan device replacement. Alarm
can be acknowledged (see chapter
„Reset menu 3: Changeover“ on p.
59)
3.13 Changeover due to overcurrent or short
circuit detected. These changeovers reduce
the life of the device. Currents exceeding
130 A are considered to be overcurrents or
short-circuit currents.
Have qualified personnel assess the
short-circuit load.
Contact the Bender service. Alarm
can be acknowledged (see chapter
„Reset menu 3: Changeover“ on p.
59)
3.50 Service alarm has been reset. Only displayed
in the service logger menu.
No action required.
4.61...4.66 Switch state error: Deviation between the
target position of the switching logic and
the reported position. This error occurs
when the required input voltage is detected
to have failed during the changeover.
Reset, perform test changeover. If
no error is displayed: OK
Check supply voltage or current
limitation (17 A are required for
switching)
If error continues to exist: Replace
device immediately
6.xx, 7.xx, 8.1x Device error. The internal self monitoring of
the device has detected a fault which could
impair the safe operation of the device.
Replace device immediately.

Table of Contents