84 ATICS-2-ISO_D00046_04_M_XXEN / 03.2021
Troubleshooting
Fault/message Description Action
Device error +
error code
For details about actions to be taken, refer to table section "Error code/service code“.
The message is on channel 6 of the BMS bus.
Short circuit distribu-
tion board
Short circuit detected Eliminate short circuit
Failure distribution
board
No voltage on line 3, contact of the change-
over switch defective. The fault can also be
caused by an (impermissible) connection
between GND, k or l and PE.
Replace ATICS®.
Separate connection between GND,
k or l and PE.
Overcurrent I(3) Overcurrent detected by measuring current
transformer STW3
Eliminate cause of overcurrent.
Eliminate any damage.
CT connection Short circuit or interruption of connecting
wire has been detected. Measuring current
transformer STW3, channel 7
Check connecting wire of measuring
current transformer.
No master There is no device with master function or
back-up master (device with address "1")
available on the RS-485 interface
Check BMS bus connection.
Check whether the master has failed
or whether its address has changed.
If the device is operated without a
BMS bus, the "Failure monitoring"
(see chapter „Settings menu 9: Inter-
face“ on p. 77) must be disabled.
Service by __
(date)
Reminder for next service Schedule appointment with the
Bender service.
Functional test
by __ (date)
Reminder for next test Schedule appointment for next test.
Perform test.
Manual mode Message "Manual mode" although manual
mode has not been enabled
Check the connections of the digital
input
Error during
changeover process
Occurs when the test set-ups do not supply
sufficient current for switching the coils of
the ATICS®.
Only use test set-ups that provide
the necessary peak current of 17 A.