ATICS-2-63A-ISO
5.3 Addressing examples
i
Use terminating resistors correctly
Communication via the BMS bus is only guaranteed when there is a terminating resistor at the be-
ginning and at the end of the BMS bus. Other terminating resistors cause malfunction and must not
be used. Please note the information in the "BMS bus" manual.
An automatic transfer switching and monitoring device with an MK… and a TM…
Device Parameter Address settings for an automatic transfer switching device
ATICS® Bus address 3
MK... Address 1
Test address 3
Alarm address 3, 2*
TM800/
CP9xx
Address 2
Test address 3
Alarm address 3, 1*
* These alarm addresses are used for mutual monitoring of the MK… or TM… for device failure.