Commissioning, settings and testing
Two automatic transfer switching devices
• One with an insulation fault locator
• With one alarm indicator and test combination in each case
• And central monitoring
Device Parameter Address settings
ATICS®
for area A
Bus address 3
First MK…
(Central monitor-
ing)
Address 1
Test address 3, 6
Alarm address 2*, 3, 4**, 5*, 6
Second MK…
for area A
Address 2
Test address 3
Alarm address 1*, 3, 4**
EDS151 Bus address 4
ATICS®
for area B
Bus address 6
MK…
for area B
Address 5
Test address 6
Alarm address 1*, 6
* These alarm addresses are used for mutual monitoring of the alarm indicator and test combinations.
** Program individual alarms for each EDS channel.