EasyManua.ls Logo

Bender ATICS-2-63A-ISO - Fault and alarm messages

Bender ATICS-2-63A-ISO
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ATICS-2-ISO_D00046_04_M_XXEN / 03.2021 83
ATICS-2-63A-ISO
8 Troubleshooting
8.1 Fault and alarm messages
In the event of an alarm, the messages of the ATICS® transfer switching and monitoring device will ena-
ble you to narrow down the possible causes. Some messages may point to several causes. The follow-
ing possible faults are indicated by messages on the ATICS® display:
Plain text messages
Fault messages with error code
8.1.1 Plain text messages
Fault/message Description Action
Failure line xx (xx
stands for: 1, 2, AV, SV,
UPS, BSV), undervolt-
age or overvoltage
Voltage is no longer available on line 1 or
line 2
Channel 1 = Line 1,
Channel 2 = Line 2
Measure voltage on line xx.
Check cause.
Eliminate fault in the system.
Check the setting for voltage and
hysteresis.
Failure line 2 when
set to
System > Line G
Generator delivers no voltage
within the set time t(GenMax)
Voltage
Insulation fault IT system has insulation fault Search for insulation fault.
Eliminate fault in the system.
Overload Current consumption too high .
Sporadic indication of load current, chang-
ing without any apparent reason. The fault
can also be caused by an (impermissible)
connection between k or l and PE.
Check settings for transformer load
current.
Switch off any loads that are not
urgently needed.
Separate connection between k or
l and PE.
Overtemperature Temperature in the IT system transformer is
too high
Switch off any loads that are not
urgently needed.
CT connection Short circuit or interruption of connecting
wire has been detected: measuring current
transformer STW2 (T4), isolating transform-
er load, channel 10
Check connecting wire of measuring
current transformer.
System connection Connection to the IT system interrupted
or voltage in the system being monitored
below 150 V
Check connection of ports L1/IT,
L2/IT to the IT system.
Check voltage in the IT system
Earth connection Connection to PE interrupted
Impermissible connection Z1 or Z2 to PE
Check that connections E and KE
are each connected to PE with two
separate lines.
Ensure that Z1 and Z2 are not con-
nected to PE.

Table of Contents