64 ATICS-2-ISO_D00046_04_M_XXEN / 03.2021
Menu mode: Operation and setting
Menu Description
13. Line 1: 50.0Hz
Line 1: Measured value frequency
14.
Line 2: 50.0Hz
Line 2: Measured value frequency
15.
t(1->2): 356ms
Changeover period t(1->2) of the last test
16.
TEST: 02.07.19
Next TEST by (date)
17.
Service: 11.07.19
Next service by (date)
The following different channel assignment applies to the "Test" setting in the "Interface/Profile" menu:
Menu Description
4. t(1->2): 356ms
Changeover period t(1->2) of the last test
7.
TEST: 02.07.19
Next TEST by (date)
8.
Service: 11.07.19
Next service by (date)
15.
t(2->1): --
Return transfer delay time is enabled, seconds counting backwards or switch-
back lock enabled
16.
I(3):5A
Load current TN system
17.
Dig.input: --
Alarm dig input/channel disabled
i
All messages (except measured value frequency) are also present on the BMS bus (see chapter
„Messages with error code or service code“ on p. 85).
7.3.2 Menu 2: Changeover
Display information on the changeover function (number, test). The device shows the alarm status for
each menu item:
= no alarm, = alarm.
Menu Description
Exit Exit "Changeover" menu; go up one menu level
1.
Changeover: xxx
Number of changeovers performed
2.
Operat. time: xxh
Operating hours counter (h=hours, d=days, mo=months)
3. Changeover I>: xx
Number of changeovers performed which were carried out with overcurrent
of short-circuit current. These changeovers reduce the service life of the ATICS®
transfer switching device.
Currents in excess of 130 A (if an STW3 is used) are considered to be overcur-
rents or short-circuit currents.