ATICS-2-ISO_D00046_04_M_XXEN / 03.2021 81
ATICS-2-63A-ISO
Menu item Function Page
2. RESET Call up reset, see chapter "Reset function" P. 58
7.3.6 Menu 6: Dig. input
This menu indicates the voltage level of the digital input.
Exit Exit "Dig. Input" menu; go up one menu
level.
- - The digital input is disabled.
0V Example: The response condition is not
met. The input has not been set.
The set function is not carried out.*
24.0V Example: The response condition is met and the response delay has elapsed. The input has
been set. The set function is carried out.*
* Whether the input is set to 0 V or 24 V depends on the set response value (see chapter P. 74).
7.3.7 Menu 7: Info
This menu displays information about the device and the software. Press the arrow button " " several
times to display all the information. Please have this information ready in case you have any queries by
telephone.
You can also reach the "INFO" menu by choosing standard display and then pressing the "INFO" button
on the front panel of the device.
Line 1: Device type
Line 2: Date, time
Line 3: Address set on the BMS bus
Line 4: Serial number of the device
Line 5…8: Software versions of the four controllers
of the device
… Bender address, website
… Exit. Exit standard information.
Exit
1. 0V
ATICS2-ISO-63
02.03.11 14:59
Address: 3
No.: 1234567890