ATICS-2-ISO_D00046_04_M_XXEN / 03.2021 73
ATICS-2-63A-ISO
Adjusting the settings:
Menu Description
Exit Exit settings menu "Relay"; go up one menu level
1. Function ALARM Relay switches if at least one of the following menus 3…12 is
set to "on" and the corresponding alarm message appears.
Active Relay switches if at least one of the following menus 3…10
is set to "on" and the corresponding alarm message does not
appear (operating message). If several of these menus are set to
"on", none of them must have an alarm in order to be able to activate the
relay.
Application example:
Function = "Active"
Line 1 = "on", all other menus (line 2, device error, etc.) are set to "off".
-> Relay is activated when line 1 is ready for operation.
GenSt Relay is used as a generator start relay
2. Relay mode N/O operation. Relay only switches in the event of an alarm.
N/C operation. Relay only switches in the event of an alarm.
N/O-T operation. Relay switches in the event of an alarm or a test.
N/C-T operation. Relay switches in the event of an alarm or a test.
3. Line 1 on Line 1
off
4. Line 2 on Line 2
off
5. Manual mode on Relay switches in manual mode (transparent cover open or digital input
"Manual mode" selected).
off
6. Device error on Internal device error 1.x, 3.x (except 3.50), 6.x, 7.x, 8.x, 9.x or BMS bus has
no master, short-circuit distribution board, failure distribution board.
off
7. Test interval on Relay switches when a test is due (interval elapsed).
off
8. Serviceinterv. on Relay switches when service is due (interval elapsed).
off
9. Dig. input on Alarm digital input. To ensure that the relay responds to the digital input,
the functions "ALARM" or "R-OPL" must be additionally set in the "Settings
-> Digital Input" menu.
off
10. Insulation on Relay switches in the event of an insulation fault
off
11. Load on Relay switches in the event of overload in the IT system
off