ATICS-2-ISO_D00046_04_M_XXEN / 03.2021 99
ATICS-2-63A-ISO
Short-circuit currents
ATICS-2-
63A-ISO...
ATICS-2-
80A-ISO...
Thermal current Ith (40 °C) 63 A 80 A
Current rated as conditional short circuit with gG fuses according to DIN
Conditional short-circuit current I
cc
(kA eff.)
Associated fuse rating (A gG)
30
80
30
100
Current rated as conditional short circuit with circuit breaker that ensures
tripping in less than 0.3 s
Current rated as short-time withstand I
cw
0.3 s (kA eff.) 7 7
Short-circuit operation (single switch)
Current rated as short-time withstand I
cw
1 s (kA eff.)
Rated peak withstand current I
cm
(kA peak)
4
17
4
17
Utilisation categories acc. to DIN EN 60947
Type Ie AC-23A Ie AC-23B Ie AC-32A Ie AC-32B Ie AC-33B
ATICS-2-63A-ISO
ATICS-2-63A-ISO-ES
63 A 63 A 63 A 63 A 63 A
ATICS-2-80A-ISO
ATICS-2-80A-ISO-ES
80 A 80 A 80 A 80 A 80 A