System description
17
MK2430_D00129_02_M_XXEN/09.2019
time there is an acoustic signal (acknowledgeable/can be muted). If a second message
is received while the first is still pending, the acoustic signal will sound again and the
messages appear alternately on the LC display. The address of the device triggering the
alarm can also be requested. The acoustic signal sounds again once a configurable
period of time has elapsed (repetition can be deactivated).
Internal device parameters (alarm addresses, test addresses…) and the parameteri-
sation of EDS and RCMS systems can be accessed via the menu system. The MK2430 can
be used as a master device in installations with several IT and EDS systems.
The "TEST" button can be used to check the function of the associated devices such as
insulation monitoring devices, LIM (Line Isolation Monitors) or GFCI (Ground Fault
Circuit Interrupters). A message will only be displayed on the MK2430 on which the
"TEST" button has been pressed. The test and its individual evaluations are carried out
sequentially. Finally, a message appears that the test was successful or a fault message
will be output.
The MK2430 has the following features:
 Display of operating status, warning and alarm messages in accordance with
IEC 60364-7-710, DIN VDE 0100-710 and other standards
 Backlit clear LC text display (4 x 20 characters)
 Standard texts for messages in 20 national languages
 200 freely programmable message texts (with TMK-SET PC software)
 Bus technology for easy installation and reduced fire load
 Acoustic alarm (can be acknowledged or muted)
 Adjustable via menu (German/English): MK2430 basic parameters
and via BMS bus: EDS46x, EDS47x, EDS49x, RCMS460, RCMS470, RCMS490
 Version for flush mounting and surface mounting
 Easy commissioning due to predefined alarm text messages
 12 digital inputs (MK2430-11 only)
 History memory with real-time clock to store 250 warnings and alarms
 Replace MK2418