Commissioning and testing
42
MK2430_D00129_02_M_XXEN/09.2019
5.3.3 Tests after parameter setting
5.4 Periodic verification and service
5.4.1 Periodic verification
The following periodic verification must be performed on electrical installations in
compliance with the local or national regulations that apply. For your Bender products,
we recommend:
Select "Test mode" from the
menu "External devices".
Are all external device
settings OK?
no
make corrections
Simulate fault messages
(e.g. device failure,
insulation fault). Generate
a fault directly or select the
"Test communication"
function. Is the fault
correctly signalled by the
MK2430?
yes
no
yes
MK2430 is ready for
operation.
make corrections
Does the MK2430 react
properly to signals at the
digital inputs?
no
make corrections