Menu mode: Operation and setting
70
MK2430_D00129_02_M_XXEN/09.2019
8.4.4 Menu 4: Control
This menu offers various options for controlling individual devices or the whole system:
8.4.4.1 Exit
Exit menu mode.
8.4.4.2 Control menu 2: Reset (AlarmClear)
Press "↵" to reset all fault messages pending on the BMS bus. "Reset done!" will then
appear in the last line.
This reset command is sent via the BMS bus. Note that some devices (e.g. PRC470) do
not respond to this reset.
Menu item Function Page
1. Exit Exit "Control" menu; go up one menu level.
2. Reset
(AlarmClear)
Resetting all fault messages pending on the BMS bus. 70
3. EDS Start/Stop Manual start/stop of test procedures on EDS system. 71
4. Test
Communication
Testing communication via the BMS bus (MK2430-11 only). 71
1.Exit
2.Reset (AlarmClear)
3.EDS start/stop
4.Test Communication
1.Exit
2.Reset (AlarmClear)
3.EDS start/stop
Reset done!