Electric Actuator ICON2000/ICON2000AD
ADDENDUM E to INSTRUCTION HANDBOOK MAN 618
© Copyright by BIFFI Italia. All right reserved. Page
11
7.4 Cable connection
Sealing of cables entries must be carried out in accordance with National
Standards or the Regulatory Authorities that have certified the extension with
additional conduit entry
Method of sealing and cable glands must be approved and separately certified
for use in hazardous areas.
Two earth points of connection, one internal and one external, are foreseen on
the base ICON2000 units enclosure for the ground cables connection.
Important
To prevent any water infiltration through the line cable
conduits, be sure the cable glands used have the minimum
degree of protection required by the plant and specified on
the actuator label.
To guarantee that the weatherproof and explosion-proof characteristics are
respected, screw the cable gland or the external ATEX certified apparatus
tightly (at least 5 turns) and block them with a thread sealant.
Important
The cables and cable glands MUST be selected
considering the maximum Temperature of the cable
indicated on the label fixed to the base ICON2000 unit.
Internal earth stud
External earth stud