EasyManuals Logo

Bitzer VARIPACK FMY+6-4 User Manual

Bitzer VARIPACK FMY+6-4
138 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #18 background imageLoading...
Page #18 background image
CB-110-418
5.8 Operating modes
The VARIPACK frequency inverter can be operated in
two different operating modes:
Capacity control of the compressor depending on an
external setpoint signal (see chapter Setpoint input
selection, page 18).
Capacity control of the compressor depending on the
evaporation pressure, which will require the optional
extension module for pressure control (see chapter
Capacity control of the compressor as a function of
the evaporation pressure, page 19).
In addition to direct evaporation pressure control, the
condenser fan can also be controlled via a 0..10V
output signal and a second compressor can be con-
nected.
5.8.1 Setpoint input selection
The VARIPACK frequency inverters can be controlled
via parameter change (P1-13) with a 0...10V (factory
setting) or 4...20mA signal.
5.8.2 Capacity control of the compressor
depending on an external setpoint signal
(P2-27)
With the "Min...Max" control characteristic, the com-
pressor starts up when the DI1 start-up command is
given. The setpoint signal provides linear frequency
control between the minimum and maximum fre-
quency of the compressor.
If a 0..10V signal is used, it must be connected
to the input AI1 (6).
If a 4..20mA signal is used, it must be connec-
ted to the input AI2 (10).
Graphical explanation of the "Min..Max" control char-
acteristic, see figure 9, page 18.
0
f [Hz]
I [mA]
4 8 12 16 20
4 .. 20 mA
f [Hz]
0 2 4 6 8 10 12
0
U [V]
0 .. 10 V
f
max
f
min
f
max
f
min
Fig.9: "Min..Max" control characteristic
Control characteristic "0..Max"
Alternatively, the control characteristic can be changed
by changing the parameter to "0..Max".
With the "0..Max" control characteristic, in addition
to the DI1 (2) start-up command, a setpoint signal of
>1% (0.1V) is required for starting the compressor.
The setpoint signal presets the frequency to a value
between 0Hz and the maximum frequency. If the
signal is >1% but lower than the minimum frequency
of the compressor, the compressor will run at the
minimum frequency.
Graphical explanation of the "0..Max" control charac-
teristic, see figure 10, page 19.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bitzer VARIPACK FMY+6-4 and is the answer not in the manual?

Bitzer VARIPACK FMY+6-4 Specifications

General IconGeneral
BrandBitzer
ModelVARIPACK FMY+6-4
CategoryInverter
LanguageEnglish

Related product manuals