170 en | Appendix Control Panels
2016.06 | 08 | F.01U.303.996 Installation and System Reference Guide Bosch Security Systems, Inc.
ZONEX 1
(Points 9 -
127
D8128D Address Switches ZONEX 2
(Points 129
– 247)+
89 - 96 OFF ON OFF ON * 209 - 216
97 - 104 OFF ON OFF OFF * 217 - 224
105 - 112 OFF OFF ON ON * 225 - 232
113 - 120 OFF OFF ON OFF * 233 - 240
121 - 127 OFF OFF OFF ON * 241 - 247
*Line termination switch. Refer to Switch 5 settings for line termination, page 170.
+Supported by the B9512 only.
Notice!
For the D8128D OctoPOPITs assigned to Points 121 to 127, 241, and 247, set Point Input
Switch 8 to the OPEN position.
The B9512G uses Points 9 to 127 on ZONEX 1 and Points 129 to 247 on ZONEX 2.
B8512G uses only Points 9 to 99 on ZONEX 1.
Switch 5 settings for line termination
If a D8125 POPEX module is connected, set switch 5 of only one D8128D to ON.
If a D8125 POPEX module is not connected, set switch 5 of all D8128Ds to OFF.
22.1.5 D8129 address settings
The D8129 connects to the control panel through a B600.
Octo-relay module address setting Control panel relay number ZONEX Number
Off-On-On-On-On 1 – 8 1
On-Off-On-On-On 9 – 16 1
Off-Off-On-On-On 17 – 24 1
On-On-Off-On-On 25 – 32 1
Off-On-Off-On-On 33 – -40 1
On-Off-Off-On-On 41 – 48 1
Off-Off-Off-On-On 49 – 56 1
On-On-On-Off-On 57 – 64 1
Off-On-On-On-On 65 – 72 2
On-Off-On-On-On 73 – 80 2
Off-Off-On-On-On 81 – 88 2
On-On-Off-On-On 89 – 96 2
Off-On-Off-On-On 97 – 104 2
On-Off-Off-On-On 105 – 112* 2*
Off-Off-Off-On-On 113 – 120* 2*