54 en | IP communications Control Panels
2016.06 | 08 | F.01U.303.996 Installation and System Reference Guide Bosch Security Systems, Inc.
Figure8.10: B426 wiring - terminal strip or interconnect wiring connector
Callout á…³ Description
1 á…³ SDI2 control panel
2 á…³ Module
3 á…³ To Ethernet network
4 á…³ Terminal strip wiring
5 á…³ Interconnect cable (P/N: F01U079745) (included)
8.3.6 Diagnostic LEDs
The B426 includes the following on-board LEDs to assist with troubleshooting:
– Heartbeat (system status).
– RX (receive).
– TX (transmit).
Refer to B426 module overview for Ethernet link LED locations.
Flash pattern Function
Flashes once every 1 sec
Normal state. Indicates normal operation state.
3 quick flashes every 1 sec
Communication error state. Indicates a bus communication
error. The module is not receiving commands from the
control panel.
On Steady
Trouble state. Indicates a trouble condition exists.
Off
LED trouble state. Module is not powered, or some other
trouble condition prohibits the module from controlling the
heartbeat LED.
Tab.8.6: Heartbeat LED descriptions