Control Panels Program and test the control panel | en 89
Bosch Security Systems, Inc. Installation and System Reference Guide 2016.06 | 08 | F.01U.303.996
– Have a point source other than Unassigned
– Have a point index not set to Disabled (must be non-zero)
– Point type must be for a Controlled Point; Part-On, Interior, or Interior Follower
– Are not service bypassed
– Are not invisible points
A controlled point can be programmed for trouble when disarmed.
Performing an intrusion walk test:
1. Choose a keypad to conduct the test. Ensure that all areas are off (disarmed).
2. Open the Main menu and then go to the [3] Actions menu > [3] Test > [1] Walk Test > [2]
Intrusion option.
3. The keypad shows the number of points that remain untested.
4. To view the list of points, press [ENTER] or [View untested points]. To scroll through the
list of points, use /[PREV] or /[NEXT].
5. When you fault a point (open a door for example), the keypad emits a brief tone and
shows the point name and that is has been tested (for example, Pt-4: P4 Follow Tested).
16.2.3 Service walk test
A service walk test allows you to walk test points assigned to any point type. The area scope
of the keypad that initiates the walk test determines which points are included in the test. All
points are included when the keypad scope is panel wide, including those with a Point Index
of 0.
A service walk test includes points:
– with a point source other than Unassigned
– that are disabled (Point Index set to 0) in addition to those that are enabled (non-zero
Point Index)
– that you have service bypassed
During a service walk test:
– The summary alarm and summary fire remain off, because there are no Fire or Burg alarm
conditions to summarize.
– The test does not generate any Extra Point troubles.
– The test does not log any Extra Point events.
Performing a service walk test:
1. Choose a keypad to conduct the test. Ensure that all areas are off (disarmed).
2. Open the Main menu and then go to the [3] Actions > [3] Test > [1] Walk Test > [3]
Service option.
3. Enter your passcode and press [ENTER]. The keypad shows the number of points that
remain to be tested.
4. To view the list of points, press [ENTER] or [View untested points]. To scroll through the
list of points, use /[PREV] or /[NEXT].
5. When you fault a point (move in front of a motion sensor for example), the keypad emits a
brief tone and shows the point name and information (for example, Area-1 Point-7
Onboard: Short).
16.2.4 Invisible walk test
An invisible walk test allows you to test both controlled points and 24-hr points. Points
assigned to Point Indexes with the Invisible Point parameter set to Yes.
An invisible walk test includes points meeting the following criteria: