34 en | Control panel installation Control Panels
2016.06 | 08 | F.01U.303.996 Installation and System Reference Guide Bosch Security Systems, Inc.
SDI2 devices daisy chained with terminal wiring
Using interconnect wiring
Interconnect wiring connectors parallel the SDI2 terminals (27 through 30 (or 23 through 26 if
configured for SDI2)). In installations with multiple SDI2 modules, using interconnect wiring
makes the installation quicker and easier than using terminal strip wiring. You use any
combination of terminal and interconnect wiring to wire multiple modules in parallel, but do
not wire a single module to the control panel using both terminal and interconnect wiring.
The interconnect wiring connectors are "keyed" (interconnect wiring plug can fit in only one
direction).