Specifications CL200
D Line transient interference
D Rapid burst pulses, symm.,
as per EN 61131-2
D 2 kV for power supply module and
digital inputs/outputs
D 1 kV for analog inputs / outputs,
counter and interrupt inputs, serial
interfaces
D Dampened sinewave 1 MHz,
symm., as per EN 61131-2
1 kV for
D NT200 power supply module
D Digital inputs / outputs
D All power supply connections on
modules
Insulation test voltage, as per
EN 61131-2
D 350 V, AC voltage
D 500 V, DC voltage
D 500 V Pulse, 1.2 / 50 ms
Shock and vibration resistance
D Sinewave-shaped oscillations on
X, Y and Z axes, to EN 61131-2
D 10 thru 57 Hz
D 0.0375 mm amplitude, contin.
D 0.075 mm amplitude, occas.
D 57 thru 150 Hz
D 0.5 g, continuous
D 1 g, occasional
D Shock loads on X, Y, and Z axes,
as per EN 61131-2
11 ms semi-sinewave 15 g
Corrosion, chemical resistance
The ambient air must be free of eleva-
ted concentrations of acids, alkali, cor-
rosives, salts, metallic vapours, or
other electrically conductive pollutants.
Pollution level, as per VDE 0110 Part1 2
The ambient air must be dustfree.
Housing and installation environments
accommodating the module rack must
comply with IP 54.
Protection category, as per EN 60529 IP 20
Safety class, as per EN 50178 Class Ι
Humidity rating, as per EN 61131-2 RH-2, 5 through 95 %, condensation
not permitted
Operating temperature range, as per
EN 61131-2, w/o battery and
MemoryCard*)
D Horizontal
installation
D 5 to +55 _C
D Vertical
installation
D 5 to +40 _C
Storage temperature range, as per
EN 61131-2
25 to +70 _C, w/o battery and
MemoryCard*)
Atmospheric pressure, as per
EN 61131-2
Operation up to 2000 m above sea
level
Transportability, as per EN 61131-2 Drop height, in package 1 m