Module Racks
3–6
1070 072 145-102 (01.07) GB
Ordering information
Designation Order no.
GG3 Module rack 1070 075 100
GG3-K Module rack 1070 079 961
Locking foot for support rail 1070 077 225
NT200 Power supply module 1070 075 096
Buffer / backup battery 1070 917 152
ZE200 Central processing unit 1070 075 169
ZE200A Central processing unit 1070 075 171
ZE200M Central processing unit 1070 075 175
ZE200AM Central processing unit 1070 075 176
ZE201 Central processing unit 1070 078 795
ZE200-DP Central processing unit 1070 078 883
ZE200A-DP Central processing unit 1070 081 448
Dummy cover 1070 075 174
3.4 Expansion Unit
. When planning an expansion, the maximum address range and the
current draw of the controller must always be observed.
The CL200 can be expanded very easily to accommodate additional modu-
les. The GG3 or GG3-K module rack is used as an expansion unit.
There are several structural options for expansion:
D Inline configuration with a maximum of 2 GG3 module racks.
D Dual inline configuration comprising one GG3 plus one GG3-K module
rack.
D Multi-row inline configuration comprising a maximum of three rows, inclu-
ding a maximum of two GG3 module racks.
D Multi-row inline configuration comprising three rows with one GG3 and
GG3-k module rack each.
The connection between two module racks is accomplished with the use of:
D Bus coupler, connecting two module racks in a row
D AG/S expansion module for interconnecting two inline rows
. Empty slots must be closed with dummy covers.