Central Processing Unit
530
1070 072 145-102 (01.07) GB
Specifications ZE200A-DPZE200-DPZE200AMZE200MZE200AZE201ZE200
Current draw from
D 5 V
for central processing unit
Typically 200 mA Typically 250 mA Typ.
650 mA
Typ.
675 mA
D Memory backup battery Typically 6 mA
D 7.5 V
for peripheral modules
Typically 1.5 mA
D 12 V ISO
for 20 mA interface
Max. 150 mA
Interfaces
D Memory PCMCIA, version 2.0,
Type 1 slot
D X31 V.24 / 20 mA interface, PG programming unit interface
D X32 Second
serial
interface
D X71 Interrupt inputs and high-speed counters
D X72 Analog I/O
as per
EN
61131-2
Analog I/O
as per
EN
61131-2
Analog I/O
as per
EN
61131-2
D X73 PROFIBUS-DP
Weight 200 g 200 g 200 g 375 g 375 g 400 g 400 g
Width 1 Slot 2 Slots
Ordering information
Designation Order no.
ZE200 Central processing unit 1070 075 169
ZE200A Central processing unit 1070 075 171
ZE200M Central processing unit 1070 075 175
ZE200AM Central processing unit 1070 075 176
ZE201 Central processing unit 1070 078 795
ZE200-DP Central processing unit 1070 078 883
ZE200A-DP Central processing unit 1070 081 448
MemoryCard 1070 917 668