92 en | Further functions Panel Controller
2017.09 | 7.0 | F.01U.258.929 User Guide Bosch Sicherheitssysteme GmbH
During the fire drill, fire alarms, fault messages and supervisory alarms are displayed.
To switch between the fire drill display and the message display in question, select Return to
message screen or Return to drill screen on the status bar.
If an alarm or a fault/supervisory alarm is sounded during a fire drill, the panel controller
reacts as described in the table below:
Fire alarm Fault/ supervisory alarm
The drill signaling devices are
switched off.
Yes No
The drill is automatically
terminated.
Yes No
Display switches to Alarm indication Fault indication
Fire drill after event ends Must be restarted
manually
Continue
A new function cannot be selected until the fault/supervisory alarm and/or the fire drill have
been completed.
20.7 Alarm Counters
Show Lifetime Event Counters
During the lifetime of the panel, the following alarm messages are counted:
– External alarm: all fire messages
– Internal alarm: all alarm messages that the panel receives in day mode
– Walktest alarm: all messages from detectors switched to walktest
To display the number of alarm messages which have been counted so far:
1. In the start menu, select Further functions
2. Alarm counters
The figure after the message type shows the number of messages counted so far.
Reset counters
You can reset the alarm counter for individual alarm types to 0.
To reset alarm counters
1. In the start menu, select Further functions
2. Alarm counters
3. Mark the alarm counter you require (e.g. external alarm)
4. Select Reset
5. Confirm the message "Attention: Counter will be reset" with OK to reset the alarm
counter to 0 or select Cancel to cancel the operation.
Notice!
In order to reset alarm counters, you need authorization level 4.