EasyManuals Logo

Brocade Communications Systems NetIron MLXe Series User Manual

Brocade Communications Systems NetIron MLXe Series
305 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #216 background imageLoading...
Page #216 background image
TABLE 44 Associations between show chassis, show fan threshold, and fan-threshold commands (continued)
show chassis command output (sensors) show fan-threshold command output (thermal
block)
fan-threshold command conguration
LP Modules (1 or 2 Trac Managers)
LP Sensor 1 reading (TM 0) THERMAL_SENSOR_TEST_RULE_LP fan-threshold lp
LP Sensor 2 reading (TM 0) THERMAL_SENSOR_TEST_RULE_LP_XPP N/A (Must not be changed)
LP Sensor 3 reading (TM 1) THERMAL_SENSOR_TEST_RULE_LP fan-threshold lp
LP Sensor 4 reading (TM 1) THERMAL_SENSOR_TEST_RULE_LP_XPP N/A (Must not be changed)
NI-MLX-10Gx8-M LP Modules
LP2 Sensor 1 reading THERMAL_SENSOR_TEST_RULE_LP_2 fan-threshold lp2
LP2 Sensor 2 reading THERMAL_SENSOR_TEST_RULE_LP_XPP2 N/A (Must not be changed)
LP2 Sensor 3 reading UNUSED UNUSED
LP2 Sensor 4 reading THERMAL_SENSOR_TEST_RULE_LP_2 fan-threshold lp2
LP2 Sensor 5 reading THERMAL_SENSOR_TEST_RULE_LP_XPP2 N/A (Must not be changed)
LP2 Sensor 6 reading UNUSED UNUSED
LP2 Sensor 7 reading UNUSED UNUSED
BR-MLX-100Gx2-X LP Modules
LP2 Sensor 1 reading THERMAL_SENSOR_TEST_RULE_LP_2 fan-threshold lp2
LP2 Sensor 2 reading THERMAL_SENSOR_TEST_RULE_LP_XPP2 N/A (Must not be changed)
LP2 Sensor 3 reading UNUSED UNUSED
LP2 Sensor 4 reading THERMAL_SENSOR_TEST_RULE_LP_2 fan-threshold lp2
LP2 Sensor 5 reading THERMAL_SENSOR_TEST_RULE_LP_XPP2 N/A (Must not be changed)
LP2 Sensor 6 reading UNUSED UNUSED
LP2 Sensor 7 reading UNUSED UNUSED
LP2 Sensor 8 reading UNUSED UNUSED
LP2 Sensor 9 reading UNUSED UNUSED
LP2 Sensor 10 reading UNUSED UNUSED
LP2 Sensor 11 reading UNUSED UNUSED
LP2 Sensor 12 reading UNUSED UNUSED
Changing the temperature polling interval
By default, the router reads the temperature sensor on each module every 60 seconds. To change the polling interval, enter the temp-
poll-period command at the global CONFIG level of the CLI.
device(config)# temp-poll-period 120
Syntax: temp poll period log threshold seconds
For the seconds parameter, you can specify a value from 30 - 120.
NOTE
Adjusting temperature polling interval out of the default setting can negatively aect the ecient cooling of blades and may
cause a blade to overheat and shutdown.
Managing the cooling system
Brocade NetIron MLXe Series Hardware Installation Guide
216 53-1004203-04

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Brocade Communications Systems NetIron MLXe Series and is the answer not in the manual?

Brocade Communications Systems NetIron MLXe Series Specifications

General IconGeneral
BrandBrocade Communications Systems
ModelNetIron MLXe Series
CategoryNetwork Router
LanguageEnglish

Related product manuals