3.4.1.2 FT1020G3 Display CP Indicators
Table 5 LED indicators on Control Panel (CP)
No.
LED Indicator
Colour
Indicating
L7 System fault Yellow
FT1020G3 is not running due to one of the following:
S/W fault
CPU fault
Memory fault
No contact between main board and MMI board
FDCIE restart (fault code ≠ 00 / 03 / 25 / 50 / 53).
L8 Test mode Yellow
One or more zones are in "test mode", see page 91 and
129.
Fault / Disablements
L9 General fault Yellow
Fault(s) in the system, i.e. not acknowledged fault(s)
and/or not corrected fault(s)
21
. See also page 128.
L10
General
disablements
Yellow Disablement(s) in the system, see page 59.
L11 Alarm devices Yellow
Steady: Output(s) type "Alarm devices" is disabled.
Flashing: One or more supervised outputs type "Alarm
devices" have generated fault(s).
This is also valid when the FDCIE has no "contact" with a
unit with such an output, e.g. 3379, 4477, 3364, etc.
L12 Fire brigade TX Yellow
Steady: Output(s) for "Routing equipment" disabled
22
via
menu (H2/B5).
Flashing: Routing equipment power supply output
23
or
one or more supervised outputs (of type "Routing
equipment" have generated fault(s). This is also valid
when the FDCIE has lost "contact" with a unit with such an
output, e.g. 3361.
Routing equipment
L13
Fault TX
activated
Yellow
One or more not acknowledged faults
24
.
Output "Fault condition" for fault TX (routing equipment) is
activated.
Test of routing equipment in progress (see menu H1).
Sensitive fault detection mode is on (see menu H5/A2).
L14
Fire brigade TX
delay
Yellow The Alert Annunciation function is enabled.
Note: Acknowledged alarm and isolated alarm are used only in the NZ convention.
21
Acknowledged or serviced fault will clear if the fault is set to non-latching in the system properties.
22
In the AU convention, it is not permitted to disable routing equipment or via the menu, only via the ASE.
23
Main board 5010 Terminal Block "J3:3-4", fuse F8 (T500mA L 250 V – TR5).
24
See also chapter “Fault acknowledge”, Page 72