Operation Manual
FT1020G3 Rev 2.4
42
9 Disable / Re-enable Alarm Devices
Outputs programmed for sounders or OWS
34
i.e. type "Alarm devices" can be collectively
disabled for all control units during Fire alarm or Alert Annunciation alarm, this is done via
menu H2/B4. The disablement is indicated by LED Fault / Disablements "General
disablements" (L10) and "Alarm devices" (L11), which are steady ON.
In case of a fire, the sounders or OWS will remain disabled, i.e. the alarm devices will not
sound until they are re-enabled again via menu H2/B4.
Note: Outputs of type "Alarm devices" cannot be individually disabled, not even via
menu H2/B2 “Disable or Re-enable Output”
See also chapters "Test of alarm devices” (H8/S4), page 135. All outputs of type "Alarm
devices" for a specified or all Control Units, can be activated for an alarm device test.
34
Including Addressable siren 3377/4477, Addressable sounder base 3379, Addressable light indicator 4383, Wireless smoke
detector 4611, and all Visual Alarm Devices 448X.