EasyManua.ls Logo

Brooks firetracker FT1020G3 FDCIE - 22 Disable or Re-Enable (H2)

Default Icon
162 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation Manual
FT1020G3 Rev 2.4
93
22 Disable or Re-enable (H2)
69
A whole zone
70
, one or more alarm points within a zone and/or control outputs can be
disabled via menus H2/B1-B2. This function can be used for temporary disablement (e.g.
building maintenance, etc.).
If the function Enhanced disablement is enabled (default), disabled alarm points cannot
activate Pre-warning, fire alarm and fault.
If this function is not enabled (via EBLWin), disabled alarm points cannot activate Pre-
warning and fire alarm but fault can be generated.
An Addressable manual call point can be disabled (normally should not be disabled).
However, when a whole zone is disabled, the addressable manual call points will not be
disabled for safety reasons.
Up to 512 whole zones can be disabled via menu H2/B1.
Up to 200 alarm points (zones / addresses) can be individually disabled via menu H2/B1
(Alarm points disabled via time channels are not limited and must not be counted).
Up to 200 outputs can be individually disabled via menu H2/B2. Disabled output will stay
in (or return to) the normal condition for the output respectively. (Collectively disabled
outputs via menus H2/B3 B4 are not limited and must not be counted).
Up to 200 Interlocking outputs can be individually disabled via menu H9/C3.
It is not possible to exceed the limits. A warning will be shown:
Max. disablements reached!
Disablement not performed.
Don't forget to re-enable (via menus H2/B1-B2) or use automatic re-enablement for
zones and alarm points.
Disablements are listed in menus H4/U1 & U2 from which it can also be printed.
LED Fault / Disablements "General disablements" (L10) is indicating one or more
disablements in the system.
Disablements are also shown in the display. An example:
Zone 001 disabled
dd-mm-yyyy hh:mm
Zone 002 address 01 disabled
dd-mm-yyyy hh:mm
…….
Number of disablements in system: 2
Note: See chapter "Information Area Priority Order", page 18, for priority order.
Disablements (and faults) are indicated by a 2-sec. beep when you close the CU door.
69
The word “Disable” or “Re-enable” is used in the Australian convention while “Isolate” and “De-Isolate” are used in the New
Zealand convention.
70
When the zone control module is used, a whole zone can be disabled without entering the menu.

Table of Contents

Related product manuals