Operation Manual
FT1020G3 Rev 2.4
44
11 Disable or Re-enable Output
All control outputs (except outputs of type “Alarm devices” and "Alarm devices for
evacuation") can be individually disabled via menu H2/B2:
• Loop unit xxxxxx output x
• Control unit xx Sx
• Control unit xx Rx
• Control unit xx Expansion Board x output x
This is indicated by LED Fault / Disablements "General disablements" (L10).
They will remain disabled until they are re-enabled again via menu H2/B2.
See also chapter Output Type (H2/B3), page 98
See also chapter “Activate / Reset Outputs (H8/S8)”, page 141.
An output can be activated for an output test, even if it is disabled.