12 Disable/Re-enable Control Outputs
36
All control outputs programmed as type:
Control (general)
Fire ventilation
Extinguishing system
Interlocking
….. can be collectively disabled via menu H2/B3 for a specified control unit or all Control
Units. This is indicated by LED Fault / Disablements "General disablements" (L10).
They will remain disabled until re-enabled again via menu H2/B3.
See also chapter Activate / Reset Outputs (H8/S8)”, page 141. An output can be activated
for an output test.
See also chapter Activate / Deactivate Interlocking Output (H9/C2), page 144. An
interlocking output can be activated for an output test, even if it is disabled.
36
Terminology of Extinguishing and Ventilation has been changed in the fire brigade panel standard AS4428.3:2010.
Extinguishing re-named to “FIRE PROTECTION ACTIVATEDand Ventilation to “SMOKE CONTROL ACTIVATED”.