Operation Manual
FT1020G3 Rev 2.4
69
up: "Memory fault in program area (n)" (n=1 or 2). The unit
will not work.
FAULT: No reply Loop unit xxxxxx
The unit (e.g. a customized unit), cannot be found by the Control
Unit.
Check the unit's COM loop address (with the programming
tool 3314 / 4414).Printer not correctly connected.
Check the downloaded Site Specific Data (SSD).
The unit might be faulty.
The unit might be removed from the COM loop.
There might be a double break or short-circuit on the COM
loop.
FAULT: No reply zone: xxx address: xx
technical number xxxxxx
The unit cannot be found by the Control Unit.
Check the unit's COM loop address (with the programming
tool 3314 / 4414).
Check the downloaded Site Specific Data (SSD).
The unit might be faulty.
The detector may be removed from its base.
There may be a double break or short circuit on the COM
loop.
Valid for a wireless smoke detector 4611: Battery voltage <
2.3 V or the Base station (4620) does not receive any detector
data.
FAULT: Printer, Control Unit xx
This is valid for an FT1020G3, with printer. Control unit no. xx.
Faulty printer
Printer not correctly connected.
No paper.
Printer selected in EBLWin but no printer mounted in the
FDCIE and vice versa.
FAULT: Read / write site data (SSW), Control Unit xx
SSW = the data that is changed during operation, i.e. week average
sensor values, access codes, calibration values and event logs, in
Control Unit no. xx.
If the C.U. was powered down (i.e. mains and battery
disconnected) without first doing a Safe shut down of Control
Unit via menu H8/S6 (see page 136), this fault may be
generated when the C.U. is powered again. After fault
acknowledge the SSW will get default values and the fault will
be corrected (serviced). Supervised outputs have to be
calibrated via menu H5/A1.
Some external influence has caused a fault in the SSW. A
system software download might be required, Call for service
personnel/engineer.
FAULT: Restart Control Unit nn,
code xx, address yyyyyyyyyy
A restart has occurred in Control Unit no. nn.
SSD and S/W download will automatically be followed by a restart.
Also, you can manually do a restart, see chapter "Restart", page 88
.
Regarding the restart codes 00, 03, 13, 25, 50 &53, see chapter