Electronic card – 5710
Error Codes
2. Check B2.
- Remove connection X12. Measure B2 in X12 with the ohmmeter,
approx. 570 ohm at 20
o
C.
- Check that cable 16 is intact between X12 and terminal 4 on A1.
- Check that cable 19 is intact between X12 and terminal 7 on A1.
- Also check the connector pins on the terminals for play and oxidi-
sation.
Pump motor circuits
1. Check the fan M12 by the regulators.
2. Check the motor cables 5, 6 and 7 and the pump motor M3.
3. If everything is okay, replace A2.
Code 226 - 227
Description Overheated lift regulator
Error mode Lift regulator error
Error cause 1. Defective cooling fan
2. Defective motor cable/motor
3. Defective lift regulator
Comments Restart possible