Operating and functions
Process level (the digital inputs DI1, DI2 and DI3 are deactivated).
To choose the dosing quantity from the memory, activate the digital inputs DI1,
DI2, DI3:
State of input DI3 0 0 0 1 1 1 1
State of input DI2 0 1 1 0 0 1 1
State of input DI1 1 0 1 0 1 0 1
Associated quantity V1 V2 V3 V4 V5 V6 V7
To go back to the Process level, deactivate the 3 digital inputs DI1 to DI3.
The display alternately shows the called memory and the dosing quantity.
To start the dosing, send a pulse on the digital input DI4.
V1 00120 L
The dosing quantity is counted down (the dosing units blink).
To read the flow rate measured in the pipe, press
or
0......9
.
To read the total dosing quantity, press
or
0......9
once.
To interrupt the dosing, see Fig. 46.
00117 L
1156 L
When the dosing is finished, the device is ready for a new dosing.
V1
Fig. 45 : Doing a dosing of a quantity from the memory, in dosing mode "EXT. MEM."
English
Type 8025 - 8035 - SE35 BATCH