EasyManua.ls Logo

Burkert ME43 - Technical Specifications; EU Conformity; Applicable Standards; Operating Environment Conditions

Burkert ME43
67 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11
Technical data
Type ME43
6 TECHNICAL DATA
6.1 Conformity
The device conforms to the EU Directives as per the EU Declaration of Conformity (if applicable).
6.2 Standards
The applied standards, which are used to demonstrate conformity with the EU Directives, are listed in the EU
typeexaminationcerticateand/ortheEUDeclarationofConformity(ifapplicable).
6.3 Operating conditions
WARNING!
Riskofinjuryduetomalfunctionifdeviceusedoutdoors.
Do not use the device outdoors and avoid heat sources which may cause the permitted temperature
range to be exceeded.
Permitted ambient
temperaturerange. -20°Cto+60°C
Operating altitude: up to 2000 m above sea level
6.4 Mechanical data
Dimensions: Refer to data sheet for Type ME43
Housing material: Polycarbonate
6.5 Electrical data
Supply voltage: 24 V ±10 % - residual ripple 10%
Power consumption < 2 W
Degree of protection: IP 20 according to EN 60529 / IEC 60529
(only if cables, plugs and sockets have been connected correctly)
veriedbyBürkert,notevaluatedbyUL
Protection class: 3 according DIN EN 61140 (VDE 0140)
Interfaces 1 spring-type terminal 5-pin for supply voltage and büS connection
PROFIBUS version: 1 plug-in connector D-Sub, 9-pin
CC-LINK version: 1 plug-in connector D-Sub, 9-pin
Industrial Ethernet version: 2 sockets for RJ45 plug-in connector
ULDevices: Limited Energy Circuit (LEC) according to UL/ IEC 61010-1
Limited Power Source (LPS) according to UL/ IEC 60950
SELV/ PELV with UL Recognized Overcurrent Protection dimensioned
accordingtoUL/IEC61010-1Table18
NEC Class 2 power source
english

Table of Contents