25
Start-up
Type ME43
8.4.6 Fieldbus-specic address mapping
→ Checkeditableeldsandcompleteifnecessary.
Theprotocol-specicsettingsareexplainedinthefollowingscreenshots (“Figure 11” to “Figure 15”).
→ Select Next.
Ifmultipleprotocolsareselectedthecorrespondingprotocol-speciccongurationpagesthen
appear (see “Figure6:Conguration,selecttargetprotocol”).
AdressmappingforEtherNet/IP:
EtherNet/IP settings
Create a gateway conguration
EthernetIP Data
Order number
Major Revision
EtherNet/IP-EDS revision
EtherNet/IP product code
1
1.1
1.1
Addressing
Automatic EtherNet/IP addressing
NextCancelBack
Minor Revision
7
EtherNet/IP product type
Generic Device,keyable (43)
^
Start
Reset device
Cyclic Name Index SubIndex Assembly Connection Class (hex) Instance (hex) Attribute (hex)
EVA_POS 0x2540 0x01 0x64 1 0x64 0x01 0x03
EVA_NamurStatus 0x2541 0x01 0x64 1 0x64 0x01 0x03
EVA_CMDdigital 0x2500 0x01 0x65 1 0x65 0x01 0x03
Device Status NamurNE107 0x2004 0x01 0x66 2 0x66 0x01 0x03
Control Word 0x3C32 0x01 0x67 2 0x67 0x01 0x03
Fieldbus-specicdevicedataandaccessdata
Automatic EtherNet/IP addressing
Start: Perform automatic EtherNet/IP addressing again
Resetdevice: Resets the values of columns 5 to 9 to 0.
Overview of EtherNet/IP addressing
Figure 11: Gateway conguration; Adress mapping EtherNet/IP