13
Technical data
Type ME43
Transmission speed 10 and 100 Mbit/s
Duplex transmission Half Duplex, full Duplex, autonegotiation
MDI modes MDI, MDI-X, Auto-MDIX
Data transport layer Ethernet II, IEEE 802.3
AddressConictDetection(ACD) supported
DLR (ring topology) supported
Integrated switch supported
CIP Reset services Identity Object Reset Service of Type 0 and 1
ModbusTCPspecications
Modbus Function Codes 1, 2, 3, 4, 6, 15, 16, 23
Mode Message Mode: Server
Transmission speed 10 and 100 Mbit/s
Data transport layer Ethernet II, IEEE 802.3
EtherCATSPECIFICATIONS
Maximum number of cyclic input
and output data
512bytesinsum
Maximum number of cyclic input
data
1024bytes
Maximum number of cyclic output
data
1024bytes
Acyclic communication (CoE) SDO,
SDO master-slave
SDO slave-slave (depending on master capability)
Type Complex slave
FMMUs 8
Sync managers 4
Transmission speed 100 Mbit/s
Data transport layer Ethernet II, IEEE 802.3
6.8 PROFIBUSDPV1specications
Acyclic communication DP V1 Class 1 Read/Write
DP V1 Class 1 Alarm
DP V1 Class 2 Read/Write/Data Transport
Transmission speed
Fixedvaluesfrom9.6kbit/sto12Mbit/s
Autodetect mode is supported
Maximum size of the transmitted
data
Input data: 244 bytes
Output data: 244 bytes
english